Show/Hide

Due to a network upgrade, the Customer Self-Service Portal, online bill payments, credit card processing, and recreation class registration will be unavailable on Saturday, August 24, 2019 from 5 p.m. to 9 p.m. We apologize for any inconvenience.

Types of Backflow Preventers

Print
Press Enter to show all options, press Tab go to next option

Air Gap

Air Gap diagramAn air gap is a vertical, physical separation between the end of a water supply outlet and the flood-level rim of a receiving vessel. This separation must be at least twice the diameter of the water supply outlet and never less than one inch. An air gap is considered the maximum protection available against backpressure backflow or backsiphonage but is not always practical and can be easily bypassed.

 

 

 


Reduced Pressure Principal Assembly (RP)

Reduced Pressure Principal Assembly diagramAn RP is a mechanical backflow preventer that consists of two independently acting, spring-loaded check valves with a hydraulically operating, mechanically independent, spring-loaded pressure differential relief valve between the check valves and below the first check valve. It includes shutoff valves at each end of the assembly and is equipped with test cocks. An RP is effective against backpressure backflow and backsiphonage and may be used to isolate health or non-health hazards.

 


Double Gate Double Check Valve Assembly (DGDC)

Double Gate Double Check Valve Assembly diagramA DGDC is a mechanical backflow preventer that consists of two independently acting, spring-loaded check valves. It includes shutoff valves at each end of the assembly and is equipped with test cocks. A DGDC is effective against backpressure backflow and backsiphonage but should be used to isolate only non-health hazards.

 

 


Pressure Vacuum Breaker Assembly (PVB)

Pressure Vacuum Breaker Assembly diagramA PVB is a mechanical backflow preventer that consists of an independently acting, spring-loaded check valve and an independently acting, spring-loaded, air inlet valve on the discharge side of the check valve. It includes shutoff valves at each end of the assembly and is equipped with test cocks. A PVB may be used to isolate health or non-health hazards but is effective against backsiphonage only.